Not intended for use on hazardous or corrosive fluids
GAUGE SPECIFICATIONS:
Pressure display range: 29 InHg to 600 psig (-98kPa to 4134 kPa)
(+/- 1 PSI to 200 psi, 0.5% to 600 psi)
Temperature display range: -40°F to 200°F (-40°C to 93°C)
Operating temperature: -10°F to 120°F (-12°C to 49°C)
(+/- 1°F * 32°F/120°F, +/- 1.5°F * -10°F/32°F)
Maximum overpressure: 800 psig (5512 kPa)
Battery life and type: 100 hours/ 9vAlkaline battery
Auto-shutoff time: 60 minutes (extended 60 minutes by upper button action)
Refrigerant data source: NIST REFRPRO software and manufacturers data
Uses one 9v Alkaline battery
(not included)
EXTENDING
AUTO-SHUTOFF TIME
Extend time by 60 minutes by
pressing upper button.
SUPERHEAT
TEMPERATURE
SENSOR
2
1
Only a properly charged unit will provide the owner
with the design SEER for maximum energy efficiency.
SUPERHEAT, TEMPERATURE,
SUBCOOLING AND PRESSURE
PUSH once to toggle between displays
PUSH 2 times to recall High, Low & Average
Hold down to clear memory.
ON/OFF
PUSH once to “Turn On”
Display shows LAST refrigerant used.
HOLD down to "Turn Off"
PUSH 2 times to select 1 hour or 24 hour auto-off mode
REFRIGERANT SELECTION
PRESS once at any time to display current refrigerant.
Continue pressing to scroll the refrigerant list.
(See list of refrigerants on page 4.)
APPLICATION TIPS:
Allow the manifold to Zero at Turn-On:
The manifold displays will zero (CAL) each time the
manifold is turned on open to atmosphere. Zeroing the gauge
compensates the Pressure display for changes in (1) Altitude
and (2) Barometric pressure.
Pressure Calibration
Don’t be alarmed if your manifold gauge does not agree
with your mechanical gauges. The digital manifold is
calibrated with a very accurate pressure and is not affected
by vibration, motion or position.
Extending On-Time
The digital manifold will turn off automatically after 60
minutes to save battery life.
If any button is touched the digital manifold will stay on for
another 60 minutes.
Over/Under-Range Indicator
Pressures or temperatures below or above the rated
ranges will cause a “1” to be displayed.
Low Battery Indicator
Low batteries will be indicated by a blinking display.
Batteries For Low Temperature Applications
Using the gauge in a low temperature conditions will
shorten battery life. Change to the 9 volt Lithium battery
(Radio Shack 23-665) to solve this problem.
SH-35N
(°F)
and SH-36N
(°C)
SUPERHEAT and SUBCOOLING GAUGE
OPERATING INSTRUCTIONS
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - OPERATING INSTRUCTIONS

Not intended for use on hazardous or corrosive fluidsGAUGE SPECIFICATIONS:Pressure display range: 29 InHg to 600 psig (-98kPa to 4134 kPa)(+/- 1 PSI to

Pagina 2 - Sample Superheat Chart

TEMP °FAWET BULB TEMPERATURE OF EVAPORATOR ENTERING AIR1. Open to atmosphere. Gauge will automatically calibrate to “Zero” for altitude and atmosphe

Pagina 3 - TESTING FOR CHARGE

A340001/4” SAE TEEW/SWIVELCOUPLERTEMPERATURESENSORSUCTION LINELIQUID LINECONDENSINGUNITREFRIGERAN TTANKQC RESTRICTORFITTINGTOLIQUID LINESERVICE VALVET

Pagina 4 - REFRIGERATION APPLICATIONS

REFRIGERATION APPLICATIONSSETTING FOR THERMOSTAT CONTROLLED CASES AND COOLERSWithout plug-ins, turn on the gauge and zero the display by holding the l